SmartArch - Occupant Density and Required Fresh Air Volume Calculation Report

This is a preliminary calculation only. Final values must be verified with the local authority, fire authority and qualified mechanical designer.

Input Panel

Report output is available only as Word (.docx).

Visual Preview

Visual Preview

Calculation Result

StatusPreliminary calculation completed
Countryfr - France / Fransa
Room / zoneOffice / work area
Area100.00 m²
Room volume300.00 m³
Occupants8
Occupant sourceCalculated by occupant-load area table
Occupant density0.080 person/m²
Rp - outdoor air per person2.36 L/s·person
Ra - outdoor air per area0.30 L/s·m²
Fresh air48.88 L/s
Fresh air175.97 m³/h
ACH0.59 1/h
Risk / noteOpen office, call center and dense work layouts require real occupant count verification.

Formula: Vbz = Rp × Pz + Ra × Az

Selected country profile summary

Occupant density basisERP / Code du travail / fire safety classification
Fresh air basisCode du travail + Règlement sanitaire + NF EN 16798
Legal modecommune_and_use_required